Producer:
Danfoss
Line: VZH
Product code: 120G0245, alternatives: 120G0250
Glass mounting:
Oil level control switch:
  • Cooling capacity (maximal speed) [kW]:
    12.68
  • Displacement [m³/h]:
    16.0
  • Refrigerant:
    R410A
  • Capacity control:
    Inverter (standard)
  • Power supply:
    400V/3Ph/50Hz
Zapytaj

Data

Technical data

Displacement
[m³/h]
16.0
Swept volume
[cm³]
44.50
Oil type
PVE 160HV, PVE 320HV
Oil charge
[l]
1.30
Internal free volume (suction)
[dm³]
3.2
Internal free volume (discharge)
[dm³]
0.5
Net weight
[kg]
27
Gross weight
[kg]
30

Electrical data

Power supply
400V/3Ph/50Hz
Maximum operating current
[A]
17.8
Rated load amps
[A]
15.5
Maximum revolutions per minute
[RPM]
6,000
Minimum revolutions per minute
[RPM]
900
Motor resistance main
[Ω]
0.71

Limits

Maximum suction pressure
[bar]
33.3
Maximum discharge pressure
[bar]
41.1
Maximum suction temperature
[°C]
55.0
Minimum suction temperature
[°C]
-35.0
Maximum discharge temperature
[°C]
65.0
Minimal discharge temperature
[°C]
-35.0

Dimensions

Suction tube diameter
[inch]
3/4
Discharge tube diameter
[inch]
1/2
Diameter
[mm]
165
Height
[mm]
415
Oil equalization
1 1/8" Rotalock
Oil drain
1/4" Flare

Other

Alternative name
VZH044CG
Approved refrigerants
R410A
Capacity control
Inverter (standard)
Protection rating ¹
IP22
Glass mounting
None
Oil level control switch
Yes
Approvals
CE, UKCA, UL

Shipped equipment

Motor protection
Frequency converter

Performance

Invalid data supplied. Correct them and try again.
Performance
Evaporation
Condensation

Cooling capacity (maximal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
5
8.18
10.26
12.75
15.71
19.18
23.22
10
7.77
9.80
12.23
15.09
18.45
22.36
26.85
15
7.36
9.34
11.69
14.46
17.71
21.47
25.81
30.77
20
6.94
8.86
11.14
13.81
16.94
20.57
24.74
29.51
34.93
25
6.52
8.38
10.57
13.15
16.15
19.63
23.64
28.22
33.43
39.31
30
6.09
7.88
9.99
12.46
15.33
18.66
22.50
26.89
31.88
37.52
43.87
35
5.64
7.37
9.39
11.74
14.48
17.66
21.32
25.51
30.28
35.68
41.76
48.56
40
6.84
8.76
11.00
13.60
16.62
20.09
24.08
28.62
33.77
39.58
46.08
45
6.28
8.10
10.22
12.68
15.53
18.82
22.59
26.90
31.79
37.32
43.51
50
7.42
9.41
11.71
14.39
17.49
21.04
25.11
29.73
34.96
40.84
55
8.54
10.69
13.19
16.08
19.40
23.21
27.56
32.48
38.02
60
9.60
11.90
14.56
17.64
21.18
25.22
29.81
35.00
65
10.46
12.88
15.68
18.91
22.61
26.82

Cooling capacity (minimal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-15
-10
-5
0
5
10
15
20
5
2.16
2.63
3.17
10
2.10
2.57
3.11
3.72
15
2.02
2.48
3.01
3.61
4.29
20
1.92
2.38
2.90
3.49
4.15
4.90
25
1.80
2.25
2.76
3.33
3.98
4.71
5.52
30
2.11
2.60
3.16
3.79
4.50
5.28
6.16
35
2.42
2.96
3.57
4.26
5.02
5.87

Power consumption (maximal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
5
2.90
2.96
2.95
2.83
2.60
2.22
10
3.14
3.25
3.30
3.26
3.11
2.84
2.41
15
3.37
3.53
3.63
3.65
3.58
3.40
3.09
2.61
20
3.62
3.80
3.94
4.02
4.03
3.93
3.71
3.35
2.83
25
3.90
4.10
4.27
4.39
4.45
4.43
4.29
4.03
3.63
3.06
30
4.22
4.42
4.61
4.77
4.87
4.91
4.85
4.68
4.38
3.93
3.30
35
4.59
4.78
4.98
5.16
5.30
5.39
5.40
5.31
5.10
4.76
4.25
3.57
40
5.20
5.39
5.59
5.76
5.88
5.95
5.93
5.80
5.55
5.16
4.60
45
5.68
5.87
6.06
6.24
6.40
6.51
6.55
6.49
6.33
6.04
5.59
50
6.41
6.59
6.78
6.96
7.10
7.18
7.19
7.10
6.90
6.56
55
7.19
7.38
7.56
7.72
7.84
7.90
7.88
7.75
7.51
60
8.05
8.23
8.40
8.55
8.65
8.68
8.62
8.46
65
8.97
9.14
9.31
9.43
9.51
9.51

Power consumption (minimal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-15
-10
-5
0
5
10
15
20
5
0.48
0.44
0.40
10
0.55
0.51
0.47
0.42
15
0.61
0.58
0.54
0.49
0.44
20
0.68
0.66
0.62
0.57
0.52
0.47
25
0.75
0.74
0.71
0.67
0.61
0.56
0.50
30
0.83
0.81
0.77
0.72
0.66
0.60
0.54
35
0.91
0.88
0.84
0.78
0.71
0.65

Application range

Legend

  • Suction gas superheating (≤ 6000 RPM): 6 K
  • Suction gas superheating (≤ 3300 RPM): 6 K
  • Suction gas superheating (≤ 2100 RPM): 6 K
  • Suction gas superheating (≤ 1500 RPM): 6 K
  • Suction gas superheating (≤ 900 RPM): 6 K
  • Current operating conditions

Dimensions

Related products

Downloads

Technical documentation, [1.8 MB]
Danfoss
08-2020
EN
Technical documentation, [674.9 KB]
Danfoss
12-2024
EN
Technical documentation, [1.4 MB]
Danfoss
09-2018
EN
Declaration, [1.3 MB]
Danfoss
06-2025
EN
Technical documentation, EN, Danfoss, 08-2020, [1.8 MB]
Technical documentation, EN, Danfoss, 12-2024, [674.9 KB]
Technical documentation, EN, Danfoss, 09-2018, [1.4 MB]
Declaration, EN, Danfoss, 06-2025, [1.3 MB]

Due to frequent changes and updates, presented data are provided on illustrative basis only. All materials contained on this website are protected by copyright and their use, copying and publishing in any form is prohibited without the written consent of Elektronika SA. Please read the full Terms of Use.

Sales of equipment

We are a direct importer, representative and authorized distributor of the world's leading refrigeration and air conditioning manufacturers. The main activity of the company is wholesale and distribution of HVACR equipment and accessories, including heat pumps and chillers, through its own network of branches.

Check our offer

Technical support

We actively support our HVACR Installers and Designers. We organize product trainings; provide assistance and technical advice to refrigeration and air conditioning engineers at every stage of the investment realization. Hundreds of successful investments confirm our competence and extensive experience.

Check our offer

Investment processes

Our organizational structures include Investment Implementation Departments, which, based on the skills of engineers and designers, in cooperation with installation companies from the investment area, are able to design and implement the most modern cooling, freezing and air conditioning units.

Check our offer