Send feedback
Report an error

Refrigeration compressor VZH088CGM

Producer:
Danfoss
Line: VZH
  • Cooling capacity (maximal speed) [kW]:
    25.52
  • Displacement [m³/h]:
    31.8
  • Refrigerant:
    R410A, R452B, R454B
  • Capacity control:
    Inverter (standard)
  • Power supply:
    400V/3Ph/50Hz
Ask about product

Data

Technical data

Displacement
[m³/h]
31.8
Swept volume
[cm³]
88.40
Oil type
POE 160SZ
Oil charge ¹
[l]
3.80
Internal free volume (suction)
[dm³]
12.7
Internal free volume (discharge)
[dm³]
0.7
Net weight
[kg]
59.02
Gross weight
[kg]
95.00

Electrical data

Power supply
400V/3Ph/50Hz
Maximum operating current
[A]
31.5
Maximum revolutions per minute
[RPM]
6,000
Minimum revolutions per minute
[RPM]
1,500
Motor resistance main
[Ω]
0.08

1 Depends on product version.

 

Limits

Maximum suction pressure
[bar]
33.3
Maximum discharge pressure ²
[bar]
48.7
Maximum suction temperature
[°C]
55.0
Minimum suction temperature
[°C]
-35.0
Maximum discharge temperature
[°C]
150.0
Minimal discharge temperature
[°C]
-35.0

Dimensions

Suction tube diameter
[inch]
1 1/8
Discharge tube diameter
[inch]
7/8
Diameter
[mm]
243
Height ³
[mm]
485
Oil equalization ³
1 3/4" Rotalock
Oil drain ³
None

2 Depends on product version.

3 Depends on product version.

Other

Product codes
120G0305, 120G0306, 120G0307, 120G0308
Alternative name
VZH088CGAMA, VZH088CGDMA
Approved refrigerants
R410A, R452B, R454B
Capacity control
Inverter (standard)
Protection rating ⁴
IP54
Glass mounting ⁵
Threaded, Installed on OEQ
Oil level control switch ⁵
None, Yes
Approvals
UL, CE, UKCA

Shipped equipment

Motor protection
Frequency converter

4 With cable gland (IP 54 only).
5 Depends on product version.

Performance

Invalid data supplied. Correct them and try again.
Performance
Evaporation
Condensation

Cooling capacity (maximal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-20
-15
-10
-5
0
5
10
15
10
23.89
29.33
35.77
43.33
15
22.94
28.28
34.56
41.92
50.44
20
21.97
27.17
33.28
40.41
48.65
58.14
25
20.97
26.02
31.92
38.79
46.73
55.87
66.30
30
19.93
24.80
30.47
37.06
44.67
53.43
63.43
74.79
35
18.85
23.51
28.93
35.21
42.47
50.81
60.36
71.22
40
17.72
22.15
27.28
33.23
40.10
48.02
57.08
67.41
45
16.53
20.70
25.52
31.11
37.58
45.03
53.59
63.37
50
15.27
19.15
23.64
28.84
34.88
41.85
49.88
59.07
55
17.50
21.63
26.43
32.00
38.47
45.94
54.52
60
19.49
23.85
28.94
34.87
41.75
49.70

Cooling capacity (minimal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-20
-15
-10
-5
0
5
10
15
20
25
10
5.88
7.24
8.84
10.72
15
5.65
6.98
8.54
10.37
12.49
20
5.40
6.70
8.21
9.98
12.03
14.38
25
5.13
6.38
7.85
9.55
11.51
13.77
16.34
30
4.84
6.05
7.45
9.08
10.95
13.11
15.57
18.35
35
4.53
5.68
7.02
8.57
10.35
12.39
14.73
17.38
20.38
40
4.20
5.30
6.56
8.02
9.70
11.63
13.83
16.34
19.18
22.37
45
3.86
4.89
6.07
7.43
9.00
10.81
12.88
15.24
17.91
20.93
50
4.45
5.54
6.80
8.26
9.94
11.87
14.07
16.57
19.41
55
4.99
6.14
7.48
9.02
10.80
12.84
15.17
17.81
60
5.45
6.65
8.05
9.67
11.54
13.69

Power consumption (maximal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-20
-15
-10
-5
0
5
10
15
10
6.77
6.76
6.64
6.36
15
7.48
7.55
7.51
7.35
7.02
20
8.19
8.32
8.36
8.29
8.08
7.70
25
8.94
9.10
9.20
9.21
9.10
8.84
8.40
30
9.73
9.91
10.06
10.14
10.11
9.96
9.64
9.13
35
10.61
10.79
10.96
11.09
11.13
11.06
10.86
10.48
40
11.58
11.76
11.94
12.09
12.18
12.19
12.07
11.81
45
12.69
12.83
13.01
13.17
13.30
13.36
13.32
13.15
50
13.94
14.05
14.19
14.35
14.50
14.59
14.61
14.52
55
15.42
15.52
15.66
15.81
15.92
15.98
15.95
60
17.02
17.12
17.25
17.37
17.45
17.47

Power consumption (minimal speed) [kW]

Evaporation temperature [°C]
Condensation temperature [°C]
 
-20
-15
-10
-5
0
5
10
15
20
25
10
1.36
1.29
1.18
1.03
15
1.57
1.52
1.44
1.31
1.14
20
1.79
1.75
1.69
1.59
1.45
1.26
25
2.02
2.00
1.96
1.88
1.76
1.60
1.38
30
2.27
2.27
2.24
2.18
2.09
1.95
1.76
1.52
35
2.56
2.57
2.55
2.51
2.44
2.33
2.16
1.95
1.67
40
2.90
2.91
2.91
2.88
2.83
2.73
2.59
2.41
2.16
1.85
45
3.29
3.31
3.31
3.30
3.26
3.18
3.06
2.90
2.68
2.40
50
3.77
3.78
3.77
3.74
3.68
3.58
3.44
3.25
2.99
55
4.32
4.31
4.29
4.25
4.16
4.04
3.87
3.64
60
4.94
4.92
4.88
4.82
4.71
4.56

Application range

Legend

  • Suction gas superheating (≤ 6000 RPM): 10 K
  • Suction gas superheating (≤ 5400 RPM): 10 K
  • Suction gas superheating (≤ 2700 RPM): 10 K
  • Suction gas superheating (≤ 1500 RPM): 10 K
  • Current operating conditions

Dimensions

Related products

Downloads

VZH scroll compressors Declaration of Conformity
Declaration, [1.5 MB]
Danfoss
01-2024
EN
VZH (M version) scroll compressors installation manual
Technical documentation, [802.6 KB]
Danfoss
05-2023
EN
VZH (M version) scroll compressors technical documentation
Technical documentation, [3.6 MB]
Danfoss
08-2023
EN
VLT frequency converter technical documentation
Technical documentation, [1.4 MB]
Danfoss
09-2018
EN
VZH scroll compressors Declaration of Conformity
Declaration, EN, Danfoss, 01-2024, [1.5 MB]
VZH (M version) scroll compressors installation manual
Technical documentation, EN, Danfoss, 05-2023, [802.6 KB]
VZH (M version) scroll compressors technical documentation
Technical documentation, EN, Danfoss, 08-2023, [3.6 MB]
VLT frequency converter technical documentation
Technical documentation, EN, Danfoss, 09-2018, [1.4 MB]

Due to frequent changes and updates, presented data are provided on illustrative basis only. All materials contained on this website are protected by copyright and their use, copying and publishing in any form is prohibited without the written consent of Elektronika SA. Please read the full Terms of Use.

Sales of equipment

We are a direct importer, representative and authorized distributor of the world's leading refrigeration and air conditioning manufacturers. The main activity of the company is wholesale and distribution of HVACR equipment and accessories, including heat pumps and chillers, through its own network of branches.

Check our offer

Technical support

We actively support our HVACR Installers and Designers. We organize product trainings; provide assistance and technical advice to refrigeration and air conditioning engineers at every stage of the investment realization. Hundreds of successful investments confirm our competence and extensive experience.

Check our offer

Investment processes

Our organizational structures include Investment Implementation Departments, which, based on the skills of engineers and designers, in cooperation with installation companies from the investment area, are able to design and implement the most modern cooling, freezing and air conditioning units.

Check our offer

Cookies information

This website uses cookies to improve the quality of the services provided. It also uses the Third-Party cookies, they provide tools and solutions that improve the ergonomics and functionality of the website, such as video playback, website usage analytics and marketing content customization.

By clicking accept, you agree to use cookies, as outlined in our Cookie Policy