Monobloc heat pump THAETP 250

Producer:
Rhoss
Line: POKER-P
  • Refrigerant:
    R290
  • Power supply:
    400V/3Ph/50Hz
  • Heating capacity (A7/W35) [kW]:
    48.60
  • Energy class (W55):
    A++
Ask about product

Data

Heating capacity

Heating capacity (A7/W35) ¹
[kW]
48.60
Power consumption - heating (A7/W35) ¹
[kW]
12.60
COP (A7/W35) ¹
3.84
Heating capacity (A7/W45) ² ⁸
[kW]
47.40
Power consumption - heating (A7/W45) ²
[kW]
14.80
COP (A7/W45) ² ⁸
3.20

Cooling capacity

Cooling capacity (A35/W7) ³ ⁸
[kW]
44.80
Power consumption - cooling (A35/W7) ³
[kW]
15.90
EER (A35/W7) ³ ⁸
2.82
Cooling capacity (A35/W18) ⁴
[kW]
60.50
Power consumption - cooling (A35/W18) ⁴
[kW]
17.10
EER (A35/W18) ⁴
3.50

Seasonal energy efficiency

SCOP (W55) ⁵
3.20
Seasonal heating efficiency (W55) ⁵
[%]
125
Energy class (W55) ⁵
A++
SCOP (W35) ⁶
3.83
Seasonal heating efficiency (W35) ⁶
[%]
150
Energy class (W35) ⁶
A++

Operating range

Ambient temperature range (heating)
[°C]
-20 — +40
Water temperature range (heating)
[°C]
+24 — +75
Ambient temperature range (cooling)
[°C]
-15 — +50
Water temperature range (cooling)
[°C]
-10 — +20

Construction

Compressor type
Scroll
Compressor quantity
2
Circuits quantity
1
Compressor step / range
2
Capacity control
Step

Others

Acoustic pressure (10m) ⁷
[dB(A)]
44.5
Refrigerant
R290
Power supply
400V/3Ph/50Hz
Net weight
[kg]
685.0

1 Ambient temperature: 7°C DB (6°C WB), water temperature: 30°C (inlet) / 35°C (outlet)
2 Ambient temperature: 7°C DB (6°C WB), water temperature: 40°C (inlet) / 45°C (outlet)
3 Ambient temperature: 35°C DB, water temperature: 12°C (inlet) / 7°C (outlet)
4 Ambient temperature: 35°C DB, water temperature: 23°C (inlet) / 18°C (outlet)

5 In medium-temperature installations, for a water temperature of 55°C
6 In low-temperature installations, for a water temperature of 35°C
7 In open field (Q = 2) at 10 m from the unit
8 Data calculated in accordance w ith EN 14511 under nominal conditions

Dimensions

1 Control panel
2 Isolator
3 Electrical Control Board
4 Compressor
5 Main heat exchanger water inlet
6 Main heat exchanger water outlet
7 Fan
8 Recovery water inlet (DS accessory) or 3-way valve (V3V)
9 Recovery water outlet (DS accessory) or 3-way valve (V3V)
10 Power supply inlet
11 Electric pump
12 Condensate drain outlet
13 Anti-vibration mounts (SAG accessory)
14 Coil protection mesh (accessory RPB)
15 Safety valve manifolds

Downloads

POKER-P heat pumps energy labels
Energy label, [186.8 KB]
Rhoss
01-2019
EN
Rhoss units Eurovent certification
Certificate, [276.2 KB]
Rhoss
01-2025
EN
POKER-P heat pumps energy labels
Energy label, EN, Rhoss, 01-2019, [186.8 KB]
Rhoss units Eurovent certification
Certificate, EN, Rhoss, 01-2025, [276.2 KB]

Due to frequent changes and updates, presented data are provided on illustrative basis only. All materials contained on this website are protected by copyright and their use, copying and publishing in any form is prohibited without the written consent of Elektronika SA. Please read the full Terms of Use.

Sales of equipment

We are a direct importer, representative and authorized distributor of the world's leading refrigeration and air conditioning manufacturers. The main activity of the company is wholesale and distribution of HVACR equipment and accessories, including heat pumps and chillers, through its own network of branches.

Check our offer

Technical support

We actively support our HVACR Installers and Designers. We organize product trainings; provide assistance and technical advice to refrigeration and air conditioning engineers at every stage of the investment realization. Hundreds of successful investments confirm our competence and extensive experience.

Check our offer

Investment processes

Our organizational structures include Investment Implementation Departments, which, based on the skills of engineers and designers, in cooperation with installation companies from the investment area, are able to design and implement the most modern cooling, freezing and air conditioning units.

Check our offer

Cookies information

This website uses cookies to improve the quality of the services provided. It also uses the Third-Party cookies, they provide tools and solutions that improve the ergonomics and functionality of the website, such as video playback, website usage analytics and marketing content customization.

By clicking accept, you agree to use cookies, as outlined in our Cookie Policy